Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DAI 1615 and BMX DAI 1615H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DAI 1615 and BMX DAI 1615H module:
Module type |
200...240 VAC inputs |
||
Operating temperature |
BMX DAI 1615 |
0...60 ºC (32...140 ºF) |
|
BMX DAI 1615H |
-25...70 ºC (-13...158 ºF) |
||
Nominal input values |
Voltage |
200...240 VAC |
|
Current |
9.7 mA (max) @ 47...53 Hz 11.5 mA (max) @ 57...63 Hz |
||
Frequency |
50/60Hz |
||
Threshold input values |
At 1 |
Voltage |
≥ 164 V |
Current |
≥ 3 mA |
||
At 0 |
Voltage |
≤ 40 V |
|
Current |
≤ 2 mA |
||
Frequency |
47...63 Hz |
||
Peak of current on enabling (at nominal U) |
380 mA |
||
Input impedance |
at nominal U and f = 55 Hz |
30 kΩ |
|
Max channel input voltage |
264 Vrms @ 63 Hz |
||
Response time |
Activation |
10 ms |
|
Deactivation |
20 ms |
||
Input type |
Capacitive |
||
Input type in compliance with IEC 61131-2 standard |
Type 1 |
||
2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant) |
|||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F) |
970 000 |
|
Fuse type |
Internal |
None |
|
External |
Fast blow fuse of 0.25 A |
||
Dielectric strength |
Channel to X-bus |
1780 V rms, 50 / 60 Hz for 1 min. |
|
Channel to channel |
1780 V rms, 50 / 60 Hz for 1 min. |
||
Resistance of insulation |
Channel to X-bus |
>10 MΩ (below 500 VDC) |
|
Channel to channel |
>10 MΩ (below 500 VDC) |
||
Sensor voltage: monitoring threshold |
OK |
> 170 V |
|
Error |
< 80 V |
||
Sensor voltage: monitoring response time |
on appearance |
20 ms < T < 50 ms |
|
on disappearance |
5 ms < T < 15 ms |
||
Power consumption 3.3 V |
typical |
76 mA |
|
maximum |
126 mA |
||
Open wire detection: current threshold |
Ok |
> 0.3 mA |
|
Erro |
< 0.2 mA |
||
Open wire shunt resistor recommendation NOTE: The external shunt resistor
is only required when the leakage current of the sensor (at OFF state)
is less than 0.3 mA. Detailed resistor calculation is provided in
the section Open Wire Detection Function.
|
200 KΩ (1W) |
||
Power dissipation |
4.3 W max. |