Altitude Operating Conditions
The characteristics in the table below apply to the module BMX DAI 0814 for use at altitude up to 2000 m (6560 ft). When the module operates above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DAI 0814 module:
Module type |
100...120 Vac inputs |
||
Operating temperature |
0...60 ºC (32...140 ºF) |
||
Nominal input values |
Voltage |
100...120 Vac |
|
Current |
5 mA |
||
Frequency |
50/60Hz |
||
Threshold input values |
At 1 |
Voltage |
≥ 74 V |
Current |
≥ 2.5 mA |
||
At 0 |
Voltage |
≤ 20 V |
|
Current |
≤ 1 mA |
||
Frequency |
47 Hz to 63 Hz |
||
Sensor supply (including ripple) |
85...132 V |
||
Peak of current on enabling (at nominal U) |
240 mA |
||
Input impedance |
at nominal U and f = 55 Hz |
13 kΩ |
|
Response time |
Activation |
10 ms |
|
Deactivation |
20 ms |
||
Input type |
Capacitive |
||
Input type in compliance with IEC 61131-2 standard |
Type 3 |
||
2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant) |
|||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F) |
1700000 |
|
Fuse type |
Internal |
None |
|
External |
Fast blow fuse of 0.25 A |
||
Power consumption 3.3 V |
typical |
61 mA |
|
maximum |
112 mA |
||
Dielectric strength |
Channel to Bus |
1780 V actual, 50 / 60 Hz for 1 min. |
|
Channel to Channel |
1780 V actual, 50 / 60 Hz for 1 min. |
||
Resistance of insulation |
Channel to Bus |
>10 MΩ (below 500 VDC) |
|
Channel to Channel |
>10 MΩ (below 500 VDC) |
||
Power dissipation |
2.35 W max. |