Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DAI 1603 and BMX DAI 1603H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DAI 1603 and BMX DAI 1603H modules:
Module type |
48 VAC inputs |
||
Operating temperature |
BMX DAI 1603 |
0...60 ºC (32...140 ºF) |
|
BMX DAI 1603H |
-25...70 ºC (-13...158 ºF) |
||
Nominal input values |
Voltage |
48 VAC |
|
Current |
5 mA |
||
Frequency |
50/60Hz |
||
Threshold input values |
At 1 |
Voltage |
≥ 34 V |
Current |
≥ 2 mA |
||
At 0 |
Voltage |
≤ 10 V |
|
Current |
≤ 1 mA |
||
Frequency |
47 Hz to 63 Hz |
||
Sensor supply (including ripple) |
40...52 V |
||
Peak of current on enabling (at nominal U) |
95 mA |
||
Input impedance |
At nominal U and f = 55 Hz |
9 kΩ |
|
Response time |
Activation |
10 ms |
|
Deactivation |
20 ms |
||
Input type |
Capacitive |
||
Input type in compliance with IEC 61131-2 standard |
Type 3 |
||
2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant) |
|||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F) |
1 303 645 |
|
Dielectric strength |
1500 V actual, 50 / 60 Hz for 1 min. |
||
Resistance of insulation |
>10 MΩ (below 500 VDC) |
||
Fuse type |
Internal |
None |
|
External |
Fast blow fuse of 0.5 A |
||
Sensor voltage: monitoring threshold |
OK |
> 36 V |
|
Error |
< 24 V |
||
Sensor voltage: monitoring response time at 24 V (-15% ... +20%) |
On appearance |
20 ms < T < 50 ms |
|
On disappearance |
5 ms < T < 15 ms |
||
Power consumption 3.3 V |
Typical |
76 mA |
|
Maximum |
107 mA |
||
Sensor supply consumption |
Typical |
466 mA |
|
Maximum |
846 mA |
||
Power dissipation |
4 W max. |