At a Glance
This parameter defines the fallback mode adopted by outputs when the PLC switches to STOP due to:
a processor error
a rack connection error
an inter-rack cable connection error
a STOP command in Control Expert.
The modes are as follows:
Mode |
Meaning |
---|---|
Fallback |
Channels are set to 0 or 1 according to the defined fallback value for the corresponding 8-channel group. |
Maintenance |
The outputs remain in the status they were in before switching to Stop. |
Procedure
The following table shows the procedure for defining the fallback mode to be assigned to a channel group.
Step |
Action |
---|---|
1 |
Open the desired module configuration screen. |
2 |
For the desired channel group, click on the arrow of the Fallback mode drop-down menu. Result : The following list appears. ![]() |
3 |
Select the desired fallback mode. |
4 |
For Fallback mode, configure each channel of the selected group. To do this, click on the drop-down menu arrow of the channel to be configured, located in the Fall Back Value column. |
5 |
Click on the desired value (0 or 1). |
6 |
Confirm the modification with the menu command. |