Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DDO 1602 and BMX DDO 1602H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DDO 1602 and BMX DDO 1602H modules:
Module type |
24 VDC positive logic static outputs |
||
Operating temperature |
BMX DDO 1602 |
0...60 ºC (32...140 ºF) |
|
BMX DDO 1602H |
-25...70 ºC (-13...158 ºF) |
||
Temperature derating |
Apply the temperature derating curve |
||
Nominal values |
Voltage |
24 VDC |
|
Current |
0.5 A |
||
Threshold values |
Voltage (including ripple) |
19...30 V (34 V possible for 1 hour/day) |
|
Current/channel |
0.625 A |
||
Current/module |
10 A |
||
Power of tungsten filament lamp |
Maximum |
6 W |
|
Leakage current |
At 0 |
< 0.5 mA |
|
Voltage drop |
At 1 |
< 1.2 V |
|
Load impedance |
minimum |
48 Ω |
|
Response time(1) |
1.2 ms |
||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86°F) |
392 285 |
|
Frequency of switching to inductive load |
0.5 / LI2 Hz |
||
Paralleling of outputs |
Yes (maximum of 2) |
||
Compatibility with IEC 61131-2 DC direct inputs |
Yes (type 3 and no type) |
||
Built-in protection |
against over voltage |
Yes, by Transil diode |
|
against inversions |
Yes, by inverted diode(2) |
||
against short-circuits and overloads |
Yes, by current limiter and electric circuit-breaker 1.5 In < Id < 2 In |
||
Fuse type |
Internal |
None |
|
External |
1 fast blow fuse of 6.3 A |
||
Pre-actuator voltage: monitoring threshold |
OK |
> 18 V |
|
Error |
< 14 V |
||
Pre-actuator voltage: monitoring response time |
on appearance |
8 ms < T < 30 ms |
|
on disappearance |
1 ms < T < 3 ms |
||
Power consumption 3.3 V |
typical |
79 mA |
|
maximum |
111 mA |
||
24 V pre-actuator consumption (excluding load current) |
typical |
23 mA |
|
maximum |
32 mA |
||
Power dissipation |
4 W max. |
||
Dielectric strength |
Output / ground or output / internal logic |
1500 V actual, 50 / 60 Hz for 1 min. |
|
Resistance of insulation |
>10 MΩ (below 500 VDC) |
||
(1) All outputs are equipped with fast demagnetization circuits for electromagnets. Electromagnet discharge time < L/R. (2) Provide a fuse to the +24 V pre-actuator supply. |