Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DDI 3202K and BMX DDI 3202KH for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DDI 3202 K and BMX DDI 3202 KH modules.
Module type |
24 VDC positive logic inputs |
||
Operating temperature |
BMX DDI 3202 K |
0...60 ºC (32...140 ºF) |
|
BMX DDI 3202 KH |
-25...70 ºC (-13...158 ºF) |
||
Nominal input values |
Voltage |
24 VDC |
|
Current |
2.5 mA |
||
Threshold input values |
At 1 |
Voltage |
≥ 11 V |
Current |
> 2 mA (for U ≥ 11 V) |
||
At 0 |
Voltage |
5 V |
|
Current |
< 0.5 mA |
||
Sensor supply (including ripple) |
19...30 V (possible up to 34 V, limited to 1 hour/day) |
||
Input impedance |
at nominal U |
9.6 kΩ |
|
Response time |
typical |
4 ms |
|
maximum |
7 ms |
||
Input type |
Current sink |
||
Input type in compliance with IEC 61131-2 standard |
Type 1 |
||
Reverse polarity |
Protected |
||
Fuse type |
Internal |
None |
|
External |
1 fast blow fuse of 0.5 A for each 16-channel group |
||
2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant) |
|||
Dielectric strength |
Primary/Secondary |
1500 V actual, 50 / 60 Hz for 1 min. |
|
Between channel groups |
500 VDC |
||
Resistance of insulation |
>10 MΩ (below 500 VDC) |
||
Paralleling of inputs |
No |
||
Reliability |
MTBF in hours at ambient temperature 30 °C (86 °F) |
696 320 |
|
Sensor voltage: monitoring threshold |
OK |
> 18 VDC |
|
Error |
< 14 VDC |
||
Sensor voltage: monitoring response time at 24 V (-15% ... +20%) |
on appearance |
1 ms < T < 3 ms |
|
on disappearance |
8 ms < T < 30 ms |
||
Power consumption 3.3 V |
typical |
121 mA |
|
maximum |
160 mA |
||
Sensor supply consumption |
typical |
92 mA |
|
maximum |
145 mA |
||
Power dissipation |
3.9 W max. |
WARNING | |
---|---|