Encoder supply
This must:
-
be reserved exclusively for supplying the encoder to avoid parasitic pulses which could interfere with the encoders, whose electronics are sensitive,
-
be placed as close to the TELEFAST 2 base as possible to reduce drops in voltage and coupling with other cables,
-
be protected against short circuits and overloads by fast blow fuses,
-
work well independently to avoid micro-power outages.
Auxiliary sensor supply
Refer to the general regulations for implementing discrete modules.
NOTE: The – 0 VDC polarity of the auxiliary encoder and sensor supplies should be grounded as near to the supplies as possible.
The shielding of the cables carrying the voltages should be grounded.