General Rules for Implementation
(Original Document)
Installation
Connecting or disconnecting the standard 15 pin SUB-D connectors of the TSX CTY 2A/ 4A/ 2C modules to/from the encoder and sensor supplies present is not recommended as this may damage the encoder. Some encoders cannot withstand sudden and simultaneous signal and supply power-ups or outages.
General wiring instructions
Wire sections
Use wires of a satisfactory section to avoid drops in voltage (mainly with 5 V) and overheating.
Example of falls in voltage for encoders supplied with 5 V with a cable length of 100 meters:
Section of the wire
Encoder consumption
50 mA
100 mA
150 mA
200 mA
0.08 mm2 (gauge 28)
1.1 V
2.2 V
3.3 V
4.4 V
0.12 mm2 (gauge 26)
-
1.4 V
-
-
0.22 mm2 (gauge 24)
-
0.8 V
-
-
0.34 mm2 (gauge 22)
0.25 V
0.5 V
0.75 V
1 V
0.5 mm2
0.17 V
0.34 V
0.51 V
0.68 V
1 mm2
0.09 V
0.17 V
0.24 V
0.34 V
Connection cable
All cables carrying the sensor supply (encoders, proximity sensor etc.) and the counting signals must:
The connection cable between the module and encoder should be as short as possible to avoid creating loops, as the circuit capacities can interfere with operation.
NOTE: If necessary, direct the flow of the signal in the same cable as the supplies. Cables with twisted pairs should preferably be used for this.