Exchanges with the bus manager are of variable exchange or message exchange type.
The addressing syntax to access the Unite messaging server is as follows:
\ bus number . connection point \ SYS
For Fipio communication, the addressing values are as follows:
-
For the bus address: always 2 for a Fipio bus,
-
For the connection point: 1 to 127 as it is possible to connect up to 127 devices on the bus.
In the following example, the bus manager addresses the Premium at connection point 4, or the Magelis at connection point 8.
Address settings of device 4: ADDR('\2.4\SYS')
Address settings of device 8: ADDR('\2.8\SYS')