2: MODULE Profibus DP
|
|||
Module identification
|
||||
Product Réf.:
|
TSX PBY 100
|
Designation :
|
Profibus DP module
|
|
Address:
|
0.2
|
Symbol :
|
||
Title of the channel
|
||||
Profibus DP Specific fonction:
|
||||
Task:
|
MAST
|
|||
Event:
|
|
|||
Profibus DP general configuration:
|
||||
Outputs:
|
Reset
|
|||
No. of IW/QW:
|
128 words
|
Diagnostics length:
|
32 bytes
|
|
Profibus DP configuration file:
|
||||
Profibus DP master configuration:
|
||||
Station address:
|
1
|
No. of slaves:
|
0
|
|
Baud rate:
|
1.5M baud
|
|
||
Slot time:
|
2000 tBit
|
Quiet Time:
|
6 tBit
|
|
Min St Delay Resp:
|
11 tBit
|
Max St Delay Resp:
|
55 tBit
|
|
Setup Time:
|
1 tBit
|
Token Rot. Time:
|
50000 tBit
|
|
Gap Update Factor:
|
1
|
Retry Limi :
|
3
|
|
Highest St Addr::
|
126
|
Min Slave Interval:
|
1 * 100 microsecondes
|
|
Polling Timeout:
|
500 ms
|
Data Control Time:
|
100 * 10ms
|
|
Profibus DP slave configuration
|
||||
Profibus DP slave langage objects
|
Slot time
|
Maximum waiting time before the master starts responding to a request.
|
Min St Delay Resp.
|
Minimum waiting time before a slave can reply (transmission delay included).
|
Setup Time
|
Waiting time between the sending of the last bit by the slave and the master’s acceptance of the response.
|
Gap Update Factor
|
Number of tokens the master uses to search for other masters on the network (for example: 10 = every 10 tokens).
|
Highest St addr.
|
The master looks for the other masters on the network masters only as far as this address. Not supported by the TSX PBY 100 module.
|
Polling timeout
|
Is only significant in exchanges between two masters. Not supported by the TSX PBY 100 module
|
Quiet time
|
Time needed for a signal to return to zero after sending a frame. During this time no devices are active on the bus.
|
Max St Delay Resp.
|
Maximum time during which the master waits for the slave to respond.
|
Token Rot. Time
|
Maximum token rotation time.
|
Retry Limit
|
When a slave does not respond, the master again asks the slave to transmit. It scans the next slave when the Retry Limit delay has been reached.
|
Min Slave Interval
|
Minimum time before a slave is re-polled.
|
Data Control Time
|
Maximum time for data exchange between the master and each slave.
|