Module configuration file
(Original Document)
At a Glance
A file describing the project configuration for the TSX PBY 100 module is available in the Control Expert documentation editor.
Illustration
It is presented in the following format:
2: MODULE Profibus DP
Module identification
Product Réf.:
TSX PBY 100
Designation :
Profibus DP module
Address:
0.2
Symbol :
Title of the channel
Profibus DP Specific fonction:
Task:
MAST
Event:
Profibus DP general configuration:
Outputs:
Reset
No. of IW/QW:
128 words
Diagnostics length:
32 bytes
Profibus DP configuration file:
Profibus DP master configuration:
Station address:
1
No. of slaves:
0
Baud rate:
1.5M baud
Slot time:
2000 tBit
Quiet Time:
6 tBit
Min St Delay Resp:
11 tBit
Max St Delay Resp:
55 tBit
Setup Time:
1 tBit
Token Rot. Time:
50000 tBit
Gap Update Factor:
1
Retry Limi :
3
Highest St Addr::
126
Min Slave Interval:
1 * 100 microsecondes
Polling Timeout:
500 ms
Data Control Time:
100 * 10ms
Profibus DP slave configuration
Profibus DP slave langage objects
Key:
Slot time
Maximum waiting time before the master starts responding to a request.
Min St Delay Resp.
Minimum waiting time before a slave can reply (transmission delay included).
Setup Time
Waiting time between the sending of the last bit by the slave and the master’s acceptance of the response.
Gap Update Factor
Number of tokens the master uses to search for other masters on the network (for example: 10 = every 10 tokens).
Highest St addr.
The master looks for the other masters on the network masters only as far as this address. Not supported by the TSX PBY 100 module.
Polling timeout
Is only significant in exchanges between two masters. Not supported by the TSX PBY 100 module
Quiet time
Time needed for a signal to return to zero after sending a frame. During this time no devices are active on the bus.
Max St Delay Resp.
Maximum time during which the master waits for the slave to respond.
Token Rot. Time
Maximum token rotation time.
Retry Limit
When a slave does not respond, the master again asks the slave to transmit. It scans the next slave when the Retry Limit delay has been reached.
Min Slave Interval
Minimum time before a slave is re-polled.
Data Control Time
Maximum time for data exchange between the master and each slave.