Lists of diagnostics variables
(Original Document)
Master diagnostics
The following table indicates the diagnostics data for the TSX PBY 100 module.
Bytes
Structure
Description
0/1
OPERATING_MODE
Master operating mode (byte 0: least significant byte; byte 1: most significant byte)
Hexadecimal values:
16#00 : inoperative (initialization)
16#40 : stop (ready to receive configuration)
16#80 : output fallback (depending on the configuration)
16#C0: operating
2/3
PNO_IDENTIFIER
Master identification code depending on the Profibus DPcode (byte  2 : least significant byte; byte 3: most significant byte)
Hexadecimal values:
16#1654 : for the TSX PBY 100 module
4
PC card
hardware version
Hardware version of the PCMCIA card depending on the Profibus DPcode
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
16#FF: no card or card invalid
5
PC card
firmware version
Software version of the PCMCIA card depending on the Profibus DPcode
Hexadecimal values:
16#14 : version V5.02I
16#16 : version V5.02K
16#XY: version V5.XY
16#FF: no card or card invalid
6
PBY
hardware version
Hardware version of the TSX PBY 100 module
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
7
PBY
firmware version
Software version of the TSX PBY 100 module
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
8
PBY IE
version
Index of software version for the TSX PBY 100 module
Hexadecimal values:
16#04 : version IE04
16#XY: version IEXY
9...15
PC card
firmware
version (ASCII)
Software version of the PCMCIA card in ASCII mode
Master Class 2 diagnostics
For Profibus DP, a Master Class 2 device has the following standard TSX PBY 100 module diagnostics data:
Bytes
Structure
Description
0
OPERATING_MODE
Master operating mode
Hexadecimal values:
16#00 : inoperative (initialization)
16#40 : stop (ready to receive configuration)
16#80 : output fallback (depending on the configuration)
16#C0: operating
1/2
PNO_IDENTIFIER
Master ID code depending on the Profibus DPcode (byte  1 : least significant byte; byte 2: least significant byte)
Hexadecimal values:
16#1654 : for the TSX PBY 100 module
3
PC card
hardware version
Hardware version of the PCMCIA card depending on the Profibus DPcode
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
16#FF: no card or card invalid
4
PC card
firmware version
Software version of the PCMCIA card depending on the Profibus DPcode
Hexadecimal values:
16#14 : version V5.02I
16#16 : version V5.02K
16#XY: version V5.XY
16#FF: no card or card invalid
5
PBY
hardware version
Hardware version of the TSX PBY 100 module
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
6
PBY
firmware version
Hardware version of the TSX PBY 100 module
Hexadecimal values:
16#10 : version V1.0
16#XY: version VX.Y
NOTE: The most and least significant diagnostics bytes of the PNO_IDENTIFIER are transposed in relation to the standard diagnostics on Profibus DP.