Definition
This parameter
corresponds to the wait time delay of the OUT_IN_MBUS
block prior to receiving a correct response from a slave device
(PLC, modem, etc.).
When the response is not completely structured in the assigned time, the block generates an error. This system allows no response after this delay.
The base time is 100 ms. The valid values are between 0 (infinite wait) and 32767.
The timeout begins after the last character of the message is sent.