At a Glance
The following
example illustrates the WRITE_VAR
function with a
management parameter check.
Programming the function
Programming in ST:
IF NOT %M20 AND %I0.1.2 THEN
%MW200:4:= 0;
INC %MW1700
%MW202:= 50;
WRITE_VAR(ADDR(’0.3.1.7’),’%MW’,20,1,%MW1700:1,%MW200:4);
SET %M20;
END_IF;
the input bit %I0.1.2 controls the function,
the internet bit %M20 is used to test the activity of the function,
%MW200:4:= 0;
sets the management table to 0,INC %MW1700;
increments the word %MW1700,MW202:= 50;
initializes the timeout value to 5 seconds.
NOTE:
WRITE_VAR(ADDM(‘0.3.1.7’),’%MW’,20,1,%MW1700:4,%MW200:4);
syntax must be used for Modicon M340 PLCs as ADDR
function cannot be used by a Modicon M340 PLC.Programming the exchange check
Programming in ST:
IF %M20 AND NOT %M200.0 THEN
INC %MW204;
IF %MW201 = 0 THEN
INC %MW205;
ELSE
SET %Q0.2.2;
INC %MW206;
%MW207 := %MW201;
END_IF;
END_IF;
%MW204 counts the number of exchanges,
%MW205 counts the number of correct exchanges,
%MW206 counts the number of exchanges generating errors,
%MW207 stores the error message,
%Q0.2.2 indicates an exchange failure.