Application-linked Modbus Parameters
(Original Document)
At a Glance
After configuring the communication channel, you need to enter the application parameters.
These parameters are accessible from three configuration zones:
The Type Zone
This configuration zone appears on the screen as shown below:
This zone enables you to select the type of Modbus Serial to be used:
The Master Zone
The configuration zone shown below is only accessible when "Master" is selected in the "Type" zone:
This zone enables you to enter the following parameters:
NOTE: The Answer delay of the Master must be at least equal to the longest Answer delay of the Slaves present on the bus.
The Slave Zone
The configuration zone shown below is only accessible when "Slave" is selected in the "Type" zone:
This zone enables you to enter the processor’s slave number.
The default value is 1.
Possible values range from 1 to 247.
NOTE: In a Modbus Slave configuration, an additional address, number 248, can be used for a point-to-point serial communication.