Installation
(Original Document)
Required Hardware
Installing the TSX SCA 64 device requires the following:
Procedure
The labels in the text below correspond with those found in the description of the device.
Step
Action
1
Unscrew screw 1 with a PZ01 screwdriver, open cover 2.
2
Fix one of the following device connection bases to its support:
  • DIN AM1-DP200 or AM1-DE 200 profile
  • board or panel, and secure with 2 M4 screws (min. length 20mm)
3
Prepare main cables 14 and 16 according to the connection type selected, as indicated on the following pages.
4
Position the ground clamps 4 onto the cables.
5
Position the ground link 5, if necessary, according to the type of connection selected, as indicated on the following pages.
6
Connect the main cables (and the power supply cable if necessary) to terminal 11 according to the type of connection selected, as indicated on the following pages.
The cable wires should have DZ5-CE005 cable ends (for the main cables) and DZ5-CE007 cable ends (for the power supply cable).
Use a 2.5mm wide flat tipped screwdriver.
Torque on terminal screw 0.25 N.m.
7
Screw on the ground clamps and link with the screws 3, using a cross tipped PZ01 screwdriver.
8
Connect the green/yellow ground wire 17 to connection terminal 10.
9
Secure the cables with nylon clips. (Attach the green/yellow wire to the power supply cable if it is present).
10
Set the micro-switches 7 and 9 to the desired configuration; see configurations on following pages.
11
Break the scored tabs on the cover 2 to make way for the cables.
12
Mount the cover 2 and secure it with the screw 1 using a cross tipped PZ01 screwdriver.