This type of communication is available for Premium PLCs:
-
Via the terminal port associated with the RS485 physical layer
-
Via the host channel of the processor or TSX SCY 21601 module with:
-
a PCMCIA TSX SCP 111 card associated with the RS232 physical layer
-
a TSX SCP 112 PCMCIA card associated to 20 mA current loops
-
a TSX SCP 114 PCMCIA card associated with physical layers RS422 and RS485
-
Via the built-in link of the TSX SCY 21601 module associated with the RS485 physical layer
The terminal port on Premium processors can only process one communication function of type:
-
INPUT_CHAR
-
PRINT_CHAR
-
OUT_IN_CHAR
For communication via a Terminal port, the maximum frame size is 120 bytes per communication function.
The PCMCIA cards can process 8 communication functions simultaneously in Premium PLCs.
The built-in link of the TSX SCY 21601 module can process 8 communication functions simultaneously.
For communication via a PCMCIA card or built in link, the maximum frame size is 4K bytes per communication function.