Transmission Linked Modbus Parameters
(Original Document)
At a Glance
After configuring the communication channel, you need to enter the transmission parameters.
These are split into six windows:
Transmission Speed
This window looks like this:
This enables you to select the transmission speed of the Modbus protocol used by the module. This complies with the other devices:
Delay Between Frames
This window looks like this:
This is the minimum time a slave will wait before sending the response to the master (even if the response is ready, the slave will wait this time before sending the response). The Delay Between frames permits a minimum delay between all frames on the Modbus network.
You are advised to use default values for configurations without a modem or intermediary devices. Otherwise, greater values must be used.
NOTE: The default value depends on the transmission speed.
NOTE: The delay between frames should be the Default value in order to be Modbus compliant. In case a Slave is not conform, the value can be changed and should be identical for the Master and all Slaves on the Bus.
NOTE: A restriction is applied to the delay between frames value for channel 0 of modules TSX SCY 11601/21601 (see table below).
The table below shows the maximum delay between frames values, according to transmission speed:
Speed (bit/s)
Max. DBF (ms)
1200
212
2400
106
4800
53
9600
26
19200
13
Data
This window looks like this:
The Data field is used to fill in the type of coding used to communicate in Modbus. This field must be set according to the other devices:
NOTE: The value 1000 in ASCII mode corresponds to an infinite delay between characters.
Stop
This window looks like this:
The Stop field allows you to fill in the number of stop bits used for communication in Modbus. The possible values are 1 or 2 stop bits. This field is set according to the other devices.
NOTE: The default value is 1 stop bit.
Parity
This window looks like this:
This field is used to set whether a parity bit is added or not, as well as its type. The possible values are Even, Odd or none (Even by default). This field is set according to the other devices.
RTS / CTS Delay
This window looks like this:
Before a character string is transmitted, the module activates the RTS (Request To Send) signal and waits for the CTS (Clear To Send) signal to be activated.