Application linked Modbus Parameters
(Original Document)
At a Glance
After configuring the communication channel, you need to enter the application parameters.
These are split into four windows:
Type Parameter
This window looks like this:
It enables you to select the type of Modbus Protocol the module uses:
NOTE: The Immediate server parameter requires the communication function to be programmed in Control Expert.
It is valid until the box is checked.
Master Function
This window is only accessible by selecting Master:
This allows you to enter:
When sending a Broadcast EF, following EF requests will be delayed depending on the Answer delay value (after a broadcast, the Modbus master will wait for the Answer delay to be elapsed before sending other requests).This feature is available on following modules:
NOTE: The Answer delay of the Master must be at least equal to the longest Answer delay of the Slaves present on the bus.
Slave Function
This window is only accessible by selecting Slave:
This allows you to fill in the Slave number of the device:
CAUTION
UNEXPECTED BEHAVIOR OF APPLICATION
Do not use wrong address parameters. For instance:
  • Do not set an address parameter that does not correspond to the targeted equipment.
  • Do not use value higher than 98 in ADDR function (field "e" for the equipment address) when using CPU embedded serial port or TSXSCY21601 channel 0 or 1.
Failure to follow these instructions can result in injury or equipment damage.
Current Loop Function
This window looks like this:
It allows you to select a: