Automatic Replacement of a Faulty AS-i Slave
(Original Document)
Principle
When a faulty slave is replaced, the replacement slave's address can be automatically programmed if the following two conditions are met:
In this case, the TBX SAP 10 signals the fault to the PLC by indicating a configuration error on the AS-i bus.
The replacement of a faulty slave by a slave of the same type occurs without the AS-i bus having to stop, and without requiring any specific manipulation. Two options are available:
Procedure
The following table shows the procedure for identifying the address of the faulty slave :
Step
Action
1
Switch the TBX SAP 10 to diagnostic mode and check the list of active slaves (LAS).
2
On the TBX SAP 10 display block, check the number of the LED that is flashing.
Procedure
The following table shows the procedure for replacing a faulty slave :
Step
Action
1
Disconnect the faulty slave.
2
Connect an identical slave instead (with the same identification and I/O code) at address 0 or at the same address as the slave to be replaced.
Result: The TBX SAP 10 automatically assigns the address of the faulty slave to the new slave connected to the AS-i bus. It is immediately activated and operational.
3
Make sure that:
  • The I/O LED on the display block is not lit,
  • On the display block, the LED of the address that was flashing stays permanently on,
  • The fault sent to the PLC disappears.