Display Panel, Diagnostics
Original instructions
General
The display panel complies with the Premium standard
Diagnostics
Meaning of the diagnostics LEDs:
RUN
ERR
COL
ADR
TX
RX
Meaning
O
P
ns
ns
ns
ns
Module not operational.
O
F
O
O
O
O
Module not configured or configuration error.
F
F
O
O
O
O
Module running self-test.
P
O
O
O
F
O
Ethernet communication sending.
P
O
O
O
O
F
Ethernet communication receiving.
P
O
O
O
F
F
Ethernet communication in sending/receiving.
P
O
F
O
F
O
Module has detected collision.
P
O
O
P
O
O
Duplicate MAC address.
O
O
O
P
O
O
Network address beyond limits.
P = Permanently on, F = flashing, O = Off, ns = not significant