Electrical Features
Original instructions
General
Module TSX ETY 110 can be inserted into any rack slot of a Premium/Atrium station (except an X Bus offset rack). The module consumption from the supply depends on the selection made from the transceiver remote power supply option.
Table of consumption:
Voltage
Current Consumed
Dissipated Power
5 volts
Typical
Maximum
Typical
Maximum
with remote power supply (RJ45)
0.8 A
1.2 A
4 W
6 W
with remote power supply (AUI)
1.2 A
2.5 A
6 W
12.5 W
NOTE: TSX ETY 110 modules on 5 volts have high consumption when an AUI connection is used. Therefore, pay special attention to the types of devices in the rack before choosing the kind of supply.
NOTE:
The number of TSX ETY 110 modules that can be connected to a rack are listed:
  • 2 modules with AUI connection
  • 4 modules with RJ45 connection