The TSX ETY 110 module supports:
The maximum frame size depends on the type of transaction:
-
In synchronous messaging, the maximum frame size is 256 bytes.
-
In asynchronous messaging, the maximum frame size is 1 Kbyte.
The number of communication functions handled simultaneously depends on the type of profile:
-
where a TCP/IP profile is used, maximum 16 simultaneous messages
-
where an ETHWAY profile is used, maximum 16 simultaneous messages
Maximum Capacity of the Module
The module provides the following capacities:
-
in the case of ETHWAY messaging : 130 messages per second
-
in the case of X-Way messaging on TCP/IP : 140 messages per second
-
in the case Modbus messaging on TCP/IP : 100 messages per second
A common word message is equivalent to 0.5 data messages.
Example of application dimensioning :
Five stations exchange common words every 100 ms and X-Way messaging on TCP/IP.
The flow of common words received by each module is:
So the remaining maximum capacity on each module on TCP-IP is:
140 – 25 + 115 messages per second
Elsewhere in this guide is a detailed discussion of
common words.