Maximum Configuration
Original instructions
Overview
The maximum configuration is determined by:
BMECXM Limits
If one of these limits is reached, the maximum capacity of the configuration is reached. In that case, you can add another BMECXM module in the architecture.
This table shows the maximum configuration of the BMECXM module:
Parameter
Maximum value
Number of devices supported
63
Number of PDO
  • 256 IN
  • 256 OUT
NOTE: For more information, refer to device PDO Allocation.
Process image size
4 Kb IN and 4 Kb OUT
BMECXM configuration file (prm file on FDR server)
64 Kb
M580 Limits
This table shows how the maximum configuration can depend on other limits:
Parameter
Depends on
Number of Ethernet slots
Rack type
Number of racks
Scanner capacity
CPU type for:
  • Number of RIO and DIO equipment supported
  • IN and OUT memory capacity
NOTE: All the resources are shared with all the other equipment that is configured on Ethernet I/O.
If these limits are reached, you can distribute the equipment between the RIO or DIO scanner of the CPU or add DIO scanners to the architecture.