MHS 80C154 Hardware platform
-
Uses standard AS-i function library
-
All the AS-i data exchange and management functions are in a Programmable Integrated Controller (PIC)
-
Module level information as status and command
Firmware Interface Definition
AS-i module configuration:
-
2 Words for List of Projected Slaves (LPS) from PLC
-
16 words for slave profile (ID and IO codes) send by the PLC
-
8 words for slave parameters
AS-i Module Input and Output
Module to PLC:
-
8 Words for input data from AS-i Bus
-
2 Words for List of Activated Slaves LAS
-
2 Words for List of Detected Slaves LDS
-
1 Word for Status information
PLC to Module: