Characteristic
|
Value
|
---|---|
AS-i bus maximum cycle time
|
5 ms
|
Maximum number of slaves on the AS-i bus
|
31
|
Maximum length of AS-i bus (all branches mixed without repeater)
|
100 meters
|
Maximum Number of Inputs/Outputs
|
124 inputs/124 outputs
|
Nominal supply voltage for AS-i bus
|
30 V DC
|
Characteristic
|
Value
|
---|---|
Calculation of AS-i scanning time for n slaves (normal operation)
|
156 μs x (n+2) if n < 31
156 μs x (n+1) if n = 31
|
Power consumption 5V PLC
|
Typically 185 mA / 250 mA maximum
|
Power consumption 30 V AS-i
|
Typically 105 mA / 120 mA maximum
|
Protection from polarity inversion on AS-i bus inputs
|
Yes
|
Degree of protection
|
IP20
|
Operating temperature
|
0 to 60 degrees Celsius
|
AS-i master profile
|
M2
|
Standards and service conditions
|
Compliant with those for Quantum PLCs
|