AS-i power supply module/block
|
TSX SUP A02/A05
|
|
---|---|---|
Connection to screw terminals
max. capacity per terminal
|
mm2
|
A02:1 output terminal
A05: 2 terminals/output (24 V DC) and
1 terminal/output (30 V DC AS-i)
2 x 1.5 with cable end or 1 x 2.5
|
Temperature:
Storage
Operation
|
°C
°C
|
-
25 to +70
-10 to +60 (1)
|
Relative humidity
|
%
|
5-95
|
Cooling
|
%
|
By natural convection
|
User safety
|
SELV (EN 60950 and IEC1131-2)
|
|
Dielectric strength:
Primary/secondary
Primary/ground
Secondary/ground
|
V rms
V rms
V rms
|
3500
2200
500
|
Insulation resistance
Primary/secondary
Primary/ground
|
Mega Ohms
Mega Ohms
|
>=100
>=100
|
Leakage current
|
I<=3.5 mA (EN 60950)
|
|
Immunity to electrostatic
discharges
|
6 kV on contact/8 kV in air
(compliant with IEC 1000-4-2)
|
|
Electrical Fast Transient
|
2 kV (series mode and common mode commun on input and output)
|
|
Influence of electromagnetic
field
|
10 V/m (80 MHz at 1 GHz)
|
|
Rejected electromagnetic disturbances
|
(compliant with FCC 15-A and EN 55022 class A)
Test conditions: nominal U and I, resistive load,
cable: 1 meter horizontal, 0.8 meter vertical
|
|
Shock wave
|
Input: 4kV MC, 2kV MS Outputs: 2kV MF, 0.5 kV MS
(compliant with IEC 1000-4-5)
|
|
Vibration (2)
|
1 mm 3 Hz at 13.2 Hz 2g 57 Hz at 150 Hz
(compliant with IEC 68-2-6, FC test)
|
|
Degree of protection
|
IP 20.5
|
|
MTBF at 40°C
Lifetime at 50°C
|
H
|
100 000
|
H
|
30 000 (at nominal voltage and at 80% of nominal power)
|