AS-i power supply
|
TSX SUP A02
30 V/2.4 A AS-i
|
TSX SUP A05
24 V/7 A AS-i & 30 V/5 A AS-i
|
|||
---|---|---|---|---|---|
Primary:
|
|||||
Nominal input voltage
|
V
|
AC 100...120/200...240
|
AC 100...120/200...240
|
||
Threshold input voltage
|
V
|
AC 85...132/170...264
|
AC 85...132/170...264
|
||
Network frequency
|
Hz
|
47...63/360...440
|
47...63/360...440
|
||
Nominal input current (U=100 V)
|
A
|
1.3
|
5
|
||
Maximum inrush current (1)
|
at 100 V
|
A
|
30
|
50
|
|
at 240 V
|
A
|
30
|
50
|
||
Maximum it upon activation (1)
|
at 100 V
|
As
|
0.06
|
0.17
|
|
at 240 V
|
As
|
0.03
|
0.17
|
||
Maximum i2t upon activation (1)
|
at 100 V
|
A2s
|
4
|
8.5
|
|
at 240 V
|
A2s
|
4
|
8.5
|
||
Power factor
|
0.6
|
0.51
|
|||
Harmonic 3
|
10% (Phi=0° and 180°)
|
10% (Phi=0° and 180°)
|
|||
Efficiency at full load
|
%
|
>75
|
>80
|
||
Secondary:
|
|||||
Useful power
|
W
|
72(84) (2)
|
230 (3)
|
||
Peak nominal current
|
30 V AS-i output
24 V output
|
A
A
|
2.4(2.8) (2)
-
|
5 (3)(4)
7 (3)(4)
|
|
Output voltage
Global variation (-10°C to +60°C)
|
V
V
|
30(AS-i)
29.5 to 31.6
|
24
+/-3%
|
30(AS-i)
29.5 to 31.6
|
|
Ripple (from 10 to 500 kHz)
Ripple (from 0 to 10 kHz)
|
mV
mV
|
50
300
|
200
240
|
50
300
|
|
Startup time on resistive load
|
s
|
<2(with C=15000 micro Farads
|
<2(with C= 15000 micro Farads
|
||
Duration of mains power supply micro-cuts (5)
|
ms
|
<=10
|
<=10
|
||
Protection against
|
Short-circuits and overloads
|
fallback to 0 and automatic reactivation on disappearance of fault
|
limitation of current on each output
|
||
Overvoltage
|
V
|
peak clipping U>36
|
peak clipping U>36
|
||
Power dissipation
|
W
|
24
|
60
|