Operating temperature
|
BMX AMO 0802
|
0...60 ºC (32...140 ºF)
|
BMX AMO 0802H
|
-25...70 ºC (-13...158 ºF)
|
|
Type of outputs
|
Non-isolated high level outputs with common point
|
|
Nature of outputs
|
Current
|
|
Number of channels
|
8
|
|
Digital/Analog converter resolution
|
16 bits
|
|
Output refresh time
|
4 ms
|
|
Power supply for outputs
|
by the module
|
|
Types of protection
|
Outputs protected to short circuits and permanent overloads
|
|
Isolation:
|
||
|
Non-isolated
|
|
|
1400 VDC
|
|
|
1400 VDC
|
|
Measurement error for standard module:
|
||
|
0.10% of FS(1)
|
|
|
0.25% of FS(1)
|
|
Measurement error for ruggedized:
|
||
|
0.10% of FS(1)
|
|
|
0.45% of FS(1)
|
|
Temperature drift
|
45 ppm/°C
|
|
Monotonicity
|
Yes
|
|
Common mode rejection (50/60 Hz)
|
80 dB
|
|
Crosstalk between channels DC and AC 50/60Hz
|
> 80 dB
|
|
Non linearity
|
0.1% of FS(1)
|
|
AC output ripple
|
2 mV rms on 50 Ω
|
|
Power consumption (3.3 V)
|
Typical
|
0.35 W
|
Maximum
|
0.48 W
|
|
Power consumption (24 V)
|
Typical
|
3.60 W
|
Maximum
|
3.90 W
|
|
(1)FS: Full Scale |
Nominal variation range
|
0...20 mA, 4...20 mA
|
Available maximum current
|
21 mA
|
Analog resolution
|
0.74 µA
|
Load impedance
|
350 Ω maximum
|
Detection type
|
Open circuit(1)(2)
|
(1)The open circuit detection is physically detected by the module if the target current value is different from 0 mA. (2)Open circuit detection is enabled with the Wiring CTRL parameter. |
![]() |
RISK OF INCORRECT DATA
If a signal wire is broken or disconnected, the last measured value is kept.
Failure to follow these instructions can result in injury or equipment damage.
|