Parameters for Rack-Mounted Analog Output Modules
(Original Document)
At a Glance
Rack-mounted analog output modules include channel-specific parameters displayed in the module configuration screen.
NOTE: Parameters indicated in bold characters are part of the default configuration.
Parameters
The following table shows the available parameters for each rack-mounted analog output module.
Module
TSX ASY 410
TSX ASY 800
Number of output channels
4
8
Range
+/-10 V
0...20 mA
4...20 mA
+/-10 V
0...20 mA
4...20 mA
High-Level Display
%.. (non modifiable)
%.. (non modifiable)
Task associated to Channel
Mast / Fast / AUXi
Mast / Fast / AUXi
Group of channels affected by the task change
1 channel
2 contiguous channels
Terminal Block Detection (1)
Yes / No
Yes / No
Fallback
Fallback to 0 / Maintenance / Fallback to value
Fallback to 0 / Maintenance / Fallback to value
24V Power Supply Control (1)
-
Yes / No
Power Supply
-
Internal / External
Lower Range Overflow Control (1)
Yes / No
Yes / No
Upper Range Overflow Control (1)
Yes / No
Yes / No
Legend:
(1)
This parameter is available as a checkbox.