Parameters for Rack-Mounted Analog Input Modules
(Original Document)
At a Glance
Analog input modules include channel-specific parameters displayed in the module configuration screen.
NOTE: Parameters indicated in bold characters are part of the default configuration.
Parameters
The following table shows the available parameters for each rack-mounted analog input module.
Parameter
TSX AEY 1600
TSX AEY 800
TSX AEY 810
TSX AEY 420
Number of input channels
16
8
8
4
Channel used (1)
Yes / No
Yes / No
Yes / No
Yes / No
Scan Cycle
Normal
Fast
Normal
Fast
Normal
Fast
-
Range
+/-10 V
0..0,10 V
0...5 V
1...5 V
0...20 mA
4...20 mA
+/-10 V
0..0,10 V
0...5 V
1...5 V
0...20 mA
4...20 mA
+/-10 V
0..0,10 V
0...5 V
1...5 V
0...20 mA
4...20 mA
+/-10 V
0..0,10 V
0...5 V
1...5 V
0...20 mA
4...20 mA
Filter
0..6
0..6
0..6
-
Display
%.. / User
%.. / User
%.. / User
%.. / User
Task associated to Channel
Mast / Fast / AUXi
Mast / Fast / AUXi
Mast / Fast / AUXi
Mast / Fast / AUXi
Group of channels affected by the task change
4 contiguous channels
4 contiguous channels
4 contiguous channels
2 contiguous channels
Terminal Block Detection (1)
Yes / No
Yes / No
Yes / No
Yes / No
Lower Range Overflow Control
-
-
Yes / No
Yes / No
Upper Range Overflow Control
-
-
Yes / No
Yes / No
Lower Threshold Range Overflow
-
-
min-12.5%
min-12.5%
Upper Threshold Range Overflow
-
-
max+12.5%
max+12.5%
Threshold 0
-
-
-
0...127
Threshold 1
-
-
-
0...127
Event Processing
-
-
-
Yes / No
Legend :
(1)
This parameter is available as a checkbox.
The following table shows the available parameters for each rack-mounted analog input module (continued).
Parameter
TSX AEY 414
TSX AEY 1614
Number of input channels
4
16
Channel used (1)
-
Yes / No
Scan Cycle
-
Normal / Fast
Range
+/-10 V
0..10 V
+/-5 V
0..5 V / 0...20 mA
1..5 V / 4...20 mA
Ni1000 IEC/DIN
Pt100 IEC/DIN
Pt1000 IEC/DIN
Thermo B
Thermo E
Thermo J
Thermo K
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
0..400 Ohms
0..3850 Ohms
-13..63 mV
Thermo K
Thermo B
Thermo E
Thermo J
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
-80..+80 mV
Filter
0..6
0..6
High-Level Display
%.. / User
%.. / User
Display thermocouples and thermowells
1/10 °C / 1/10 °F / %..
1/10 °C / 1/10 °F / %..
Task associated to Channel
Mast / Fast / AUXi
Mast / Fast / AUXi
Group of channels affected by the task change
1 channel
4 contiguous channels
Terminal Block Detection (1)
Yes / No
Yes / No
Wiring Control
Active / Inactive
Active / Inactive
Cold junction compensation
Internal / External
Internal by TELEFAST / External by Pt100
Read Cold junction
Lower Range Overflow Control (1)
-
Yes / No
Upper Range Overflow Control (1)
-
Yes / No
Lower Threshold Range Overflow
-
min-12.5%
Upper Threshold Range Overflow
-
max+12.5%
High Precision (1)
-
Yes / No
Legend :
(1)
This parameter is available as a checkbox.