Under/Overflow Monitoring for the TSX ASY 800 Module
(Original Document)
Introduction
The TSX ASY 800 module allows an overflow of +/- 5% on voltage ranges and of 4 to 20 mA and + 5% on the current range.
Range under/overflow detection is optional.
Measurement Areas
The measurement range is divided in three areas:
Nominal Area 
Measurement range matching the chosen range.
Overflow Area 
Area located beyond the upper threshold.
Underflow Area 
Area located below the lower threshold.
Overflow Flags
Overflow values for the various ranges are as follows:
Range
Lower threshold
Upper threshold
+/-10V
-10500 (equals -10.5V)
+10500 (equals +10.5V)
0 to 20 mA
0 (i.e. 0 mA)
+10500 (equals +21 mA)
4 to 20 mA
-500 (equals 3.2 mA)
+10500 (equals +20.8 mA)
You may also choose the flag for an overflow of the range upper value, for an underflow of the range lower value, or for both.
If under/overflow monitoring is required, indications are provided by the following bits:
Bit Name
Meaning (when = 1)
%Ir.m.c.ERR
Denotes an error on the channel
%MWr.m.c.2.1
Denotes a range overflow on the channel :
  • %MWr.m.c.2.3 = 1 denotes an overflow of the range upper threshold,
  • %MWr.m.c.2.3 = 0 denotes an underflow of the range lower threshold.