Measurement Filtering
(Original Document)
Introduction
The type of filtering performed by the system is called "first order filtering." The filtering coefficient is editable through the Control Expert screen or through a program.
Mathematical Formula
The applicable mathematical formula is as follows:
where:
α = filter efficiency,
Mesf(n) = filtered measurement at time n,
Mesf(n-1) = filtered measurement at time n-1,
Valb(n) = raw value at time n.
The user configures the filtering value from among 7 possibilities. This value may be changed even when the application is in RUN mode.
NOTE: Filtering is disabled in Fast Cycle mode.
Values for the TSX AEY 414 Module
Filtering values are as follows: 
Desired Efficiency
Required Value
α corresponding
Filter Response Time at 63%
Cut-off Frequency (in Hz)
No filtering
0
0
0
0
Low filtering
1
2
0.750
0.875
1.91 s
4.12 s
0.083
0.039
Medium filtering
3
4
0.937
0.969
8.45 s
17.5 s
0.019
0.0091
High filtering
5
6
0.984
0.992
34.1 s
68.5 s
0.0046
0.0022