Measurement Filtering
(Original Document)
Introduction
The type of filtering performed by the system is called "first order filtering."
The filtering coefficient is editable from the Control Expert screen or through programming.
Mathematical Formula
The applicable mathematical formula is as follows:
where:
= filter efficiency,
Mesf(n) = filtered measurement at time n,
Mesf(n-1) = filtered measurement at time n-1,
Valb(n) = raw value at time n.
User configures the filtering value from 7 possibilities. This value may be changed even when application is in RUN mode.
NOTE: Filtering is disabled in Fast Cycle mode.
Values for TSX AEY 800 module
Filtering values are as follows :
Desired Efficiency
Required Value
corresponding
Filter Response Time at 63%
Cut-off Frequency (in Hz)
No filtering
0
0
0
0
Low filtering
1
2
0,750
0,875
100 ms
202 ms
1,591
0,788
Medium filtering
3
4
0,937
0,969
419 ms
851 ms
0,379
0,187
High filtering
5
6
0.984
0.992
1.714 ms
3.442 ms
0,093
0,046
Values for TSX AEY 1600 module
Filtering values are as follows :
Desired Efficiency
Required Value
corresponding
Filter Response Time at 63%
Cut-off Frequency (in Hz)
No filtering
0
0
0
0
Low filtering
1
2
0,750
0,875
178 ms
382 ms
0,894
0,416
Medium filtering
3
4
0,937
0,969
791 ms
1.607 s
0,201
0,099
High filtering
5
6
0,984
0,992
3.239 s
6.502 s
0,049
0,024