Input types
|
Thermocouple inputs
|
Nature of inputs
|
Multi-range
|
Number of channels
|
16
|
Acquisition cycle time:
|
Number of dual channels used x 70ms (1)
1120 ms
|
Analog / Digital converter
|
16 bits (0...65535 points)
|
Wiring test
|
8 ms
|
Digital filtering
|
1st order (time constant = 0 to 128 x module cycle time)
|
Insulation:
|
100 V rms
1000 V rms
1000 V rms
|
Insulation resistance below 500VDC between channel and ground
|
> 10 mOhms
|
Input impedance
|
> 10 mOhms
|
Linearization
|
Automatic
|
Max. voltage surge allowed in differential mode on inputs
|
+/-30 VDC
|
Common mode voltage allowed in operation:
|
250 VDC or 280 VAC
240 VAC
|
Common mode rejection between channels and ground
|
110 dB (VDC-VAC 50/60 Hz)
|
Series mode rejection at 50/60 Hz
|
100 dB
|
Cold junction compensation:
|
between -5 and +60°C
between -5 and +85°C
|
Max. line resistance for the wiring test
|
500 Ohms
|
Max. power dissipation
|
2 W
|
PLC standards
|
IEC1131, IEC801, IEC68, UL508, UL94
|
Electrical range
|
+/-80 mV
|
Sensor standards
|
IEC584, IEC751, DIN43760, DIN43710, NFC42-330
|
Legend:
|
|
(1)
|
This calculation does not take any test into account. For further information, please refer to the following manual: ...
|