Electrical Characteristics
Original instructions
Introduction
The power supply modules installed in the X80 rack delivers 2 voltages (3.3 Vdc and 24 Vdc) to supply the backplane and connected modules.
Rack Power Consumption
Rack Reference
Rack Average Current Consumption
3.3 Vdc Supply Power
24 Vdc Supply Power
BMXXBP0400(H)
304 mA (1 W)
BMXXBP0600(H)
455 mA (1.5 W)
BMXXBP0800(H)
607 mA (2 W)
BMXXBP1200(H)
225 mA (0.74 W)
BMEXBP0400(H)
49 mA (162 mW)
118 mA (2.8 W)
BMEXBP0800(H)
64 mA (211 mW)
164 mA (3.9 W)
BMEXBP1200(H)
86 mA (283 mW)
164 mA (3.9 W)
BMEXBP0602(H)
86 mA (283 mW)
164 mA (3.9 W)
BMEXBP1002(H)
86 mA (283 mW)
164 mA (3.9 W)
Mean Time Between Failures
The rack MTBF is a component of the global system MTBF:
Rack Reference
MTBF (Hours at 30 °C Continuous)
BMXXBP0400(H)
BMXXBP0600(H)
BMXXBP0800(H)
BMXXBP1200(H)
BMEXBP0400(H)
2000000
BMEXBP0800(H)
1700000
BMEXBP1200(H)
1500000
BMEXBP0602(H)
1770000
BMEXBP1002(H)
201000