When the checkbox is...
|
This page...
|
---|---|
Selected
|
|
De-selected
|
|
Step
|
Action
|
---|---|
1
|
In the DTM Browser, select the communication module and click the right mouse button. A pop-up menu opens.
|
2
|
In the menu, select Device menu → Diagnostic. The Diagnostic window opens.
|
3
|
In the left pane of the Diagnostic window, select the communication module node.
|
4
|
Click on the Bandwidth Diagnostic tab to open that page.
|
Parameter
|
Description
|
---|---|
I/O - Scanner:
|
|
EtherNet/IP Sent
|
The number of EtherNet/IP packets the module has sent, since the last reset, in packets/second.
|
EtherNet/IP Received
|
The number of EtherNet/IP packets the module has received, since the last reset, in packets/second.
|
Modbus TCP Requests
|
The number of Modbus TCP requests the module has sent, since the last reset, in packets/second.
|
Modbus TCP Responses
|
The number of Modbus TCP responses the module has received, since the last reset, in packets/second.
|
I/O - Adapter:
|
|
EtherNet/IP Sent
|
The number of EtherNet/IP packets the module has sent—in the role of a local slave—since the last reset, in packets/second.
|
EtherNet/IP Received
|
The number of EtherNet/IP packets the module has received—in the role of a local slave—since the last reset, in packets/second.
|
I/O - Module
|
|
Module Capacity
|
The maximum number of packets that the module can process, in packets per second.
|
Module Utilization
|
The percentage of communication module capacity being used by the application.
|
Messaging - Client:
|
|
EtherNet/IP Activity
|
The number of I/O messages sent by the module—using the EtherNet/IP protocol—since last reset, in packets per second.
|
Modbus TCP Activity
|
The number of I/O messages sent by the module—using the Modbus TCP protocol—since last reset, in packets per second.
|
Messaging - Server:
|
|
EtherNet/IP Activity
|
The number of I/O messages received by the module—using the EtherNet/IP protocol—since last reset, in packets per second.
|
Modbus TCP Activity
|
The number of I/O messages received by the module—using the Modbus TCP protocol—since last reset, in packets per second.
|
Module:
|
|
Processor Utilization
|
The percent of Ethernet communication module processor capacity used by the present level of communication activity.
|