Description of Attributes

The attribute is available only for the redundant PAC.

Attribute

Description

Control Mode

Defines how a redundant PAC is managed by the software.

To switch between the available modes, you must confirm your selection.

  • Primary And Standby (default):

    • Regular mode of operation for a redundant PAC.

    • The standby PAC is synchronized.

  • Primary A Only or Primary B Only:

    • Redundancy is not available.

    • The standby PAC is not synchronized.

    • The Under Construction attribute of the standby PAC is set to true and its state is not inherited from the parent device anymore.

    • You cannot deploy to the standby PAC.

    • Modifications that you perform on either redundant local rack (A or B) are still repeated on the counterpart rack (for example, modifying attribute values or changing to the rack configuration).

    • In physical views, the high-speed cable link is shown as a dotted line.