Details of T_COM_EIP IODDT
Original instructions
Exchange Objects of the IODDT
The T_COM_EIP IODDT supports both implicit and explicit exchange objects:
Exchange objects are %I, %IW, %M and %MW.
The tables below presents the various implicit and explicit exchange objects of IODDT T_COM_EIP, as supported by the BMX NOC 0401 communication module.
The parameters r, m, and c shown in the following-tables represent the topological addressing of the module. Each parameter has the following signification:
Implicit and Explicit Exchange Objects of the T_COM_EIP IODDT
The T_COM_EIP IODDT presents the following implicit communication objects:
Standard symbol
Type
Access
Description
Address
CH_ERROR
BOOL
R
Channel detected error bit
%Ir.m.c.ERR
STS_ETH_SERVICES
INT
R
Status of Ethernet services:
%IWr.m.c.0
Bit 0: EIP Scanner (0 = OK, 1 = NOK)
Bit 1: EIP Adapter (0 = OK, 1 = NOK)
Bit 2: EIP Client (0 = OK, 1 = NOK)
Bit 3: EIP Server (0 = OK, 1 = NOK)
Bit 4: Modbus scanner (0 = OK, 1 = NOK)
Bit 5: Modbus TCP Client (0 = OK, 1 = NOK)
Bit 6: Modbus TCP Server (0 = OK, 1 = NOK)
Bit 7: FDR Server (0 = OK, 1 = NOK)
Bit 8: RSTP (0 = OK, 1 = NOK)
Bit 9–Bit 15: (Reserved)
Explicit Exchange Objects of the T_COM_EIP IODDT
The T_COM_EIP IODDT presents the following explicit communication objects:
Standard symbol
Type
Access
Description
Address
EXCH_STS
INT
R
Exchange Status:
%MWr.m.c.0
STS_IN_PROGR
BOOL
R
Bit 0: Status parameter read in progress
%MWr.m.c.0.0
CMD_IN_PROGR
BOOL
R
Bit 1: Command parameter write in progress
%MWr.m.c.0.1
ADJ_IN_PROGR
BOOL
R
Bit 2: (Reserved)
%MWr.m.c.0.2
EXCH_RPT
INT
R
Channel report
%MWr.m.c.1
STS_ERR
BOOL
R
Bit 0: Error detected while reading channel status
%MWr.m.c.1.0
CMD_ERR
BOOL
R
Bit 1: Error detected while sending a command on the channel
%MWr.m.c.1.1
ADJ_ERR
BOOL
R
Bit 2: (Reserved)
%MWr.m.c.1.2
CH_FLT
INT
R
Channel faults detected
%MWr.m.c.2
NO_DEVICE
BOOL
R
Bit 0: (Reserved)
%MWr.m.c.2.0
ONE_DEVICE_FLT
BOOL
R
Bit 1: (Reserved)
%MWr.m.c.2.1
BLK
BOOL
R
Bit 2: (Reserved)
%MWr.m.c.2.2
TO_ERR
BOOL
R
Bit 3: (Reserved)
%MWr.m.c.2.3
INTERNAL_FLT
BOOL
R
Bit 4: Internal error detected: channel inoperative
%MWr.m.c.2.4
CONF_FLT
BOOL
R
Bit 5: (Reserved)
%MWr.m.c.2.5
COM_FLT
BOOL
R
Bit 6: X-bus communication error detected
%MWr.m.c.2.6
APPLI_FLT
BOOL
R
Bit 7: Application configuration error detected
%MWr.m.c.2.7
ETH_GLOBAL_STS
INT
R
Ethernet global status
%MWr.m.c.3
BOOL
R
Bit 0: detected configuration error
BOOL
R
Bit 1: (Reserved)
BOOL
R
Bit 2: duplicate IP address detected
BOOL
R
Bit 3: Configuration mismatch
BOOL
R
Bit 4: All 4 external Ethernet ports are disconnected
BOOL
R
Bit 5: The module is in the process of obtaining an IP address (BOOTP or in duplicate IP address)
IP_ADDR
DINT
R
IP address
%MWr.m.c.4