UNEXPECTED SYSTEM BEHAVIOR
Always launch ACS from Control Expert in order to synchronize variables and data between Control Expert and ACS.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
![]() |
UNEXPECTED SYSTEM BEHAVIOR
Stop the PLC before transferring an ACS configuration and/or I/O scanning modifications.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Step
|
Action
|
Results
|
---|---|---|
1
|
Open the Ethernet network configuration screen.
|
|
2
|
In the Module Utilities zone select YES for IO Scanning.
|
|
3
|
Select the I/O Scanning tab.
|
I/O Scanning screen opens.
|
4
|
Enter, on a free line, the IP address for the connection you want to use to communicate with the Advantys island.
|
|
5
|
Enter RD length and WR length on the same line. The lengths must be long enough for the expected Advantys configuration.
|
|
6
|
Validate the I/O Scanning screen.
|
|
7
|
Click on the ... button (that is next to Device Name cell on the same line).
|
The Property box opens.
|
8
|
Select STB or OTB in the Device Type drop-down menu.
|
|
9
|
Enter a Device Name (following the naming rules).
|
|
10
|
You have 2 choices:
|
Results for both 1. and 2. are:
|
11
|
After ACS opens, configure your Advantys island.
NOTE: While the ACS is open Ethernet screen is locked and cannot be edited, but the other Control Expert services can be edited. NOTE: The User Defined Label must be filled in the IO image. If not, the Advantys varialble will no be added in the Control Expert Data Editor. |
|
12
|
When your Advantys island has been built and validated, close ACS.
|
A Control Expert message box opens “Do you want to update your symbols now?”
|
13
|
You have 2 choices:
|
If you clicked on No:
|
14
|
Your Advantys island configuration is being synchronized with Control Expert.
After the synchronization is finished, you are returned to I/O Scanning. Verify that the Device Name is now displayed in black.
|
The results are:
|
15
|
Build your Control Expert application.
|
|
16
|
STOP the PLC.
|
|
17
|
Transfer:
|
|
18
|
RUN your application in the PLC.
|
|
Step
|
Action
|
---|---|
1
|
From Control Expert, open a new Advantys island in ACS.
|
2
|
In ACS, select File menu → Copy Island Contents.
|
3
|
In the Open island window, select the island file (*.isl) to copy.
|
4
|
Click on Yes in the “Do you want to proceed?” message box.
|
5
|
The message “Island file has been saved.” in the Log Window verifies that the operation was successful.
|
Step
|
Action
|
---|---|
1
|
In ACS, open an island configuration, for example, STB1.
|
2
|
Select File menu => Copy STB1 Contents
|
3
|
In the Copy STB1.isl to window, select the target directory.
|
4
|
The message “A copy of the island file has been saved with another name.” includes in the Log Window verifies that the operation was successful. The name is new because its path has changed.
|