Rack Position: BMX NOE 01x0 and BMX P34 20x0x
Original instructions
Introduction
This topic describes the appropriate rack positions of the BMX NOE 01•0 modules and BMX P34 20x0x CPUs on a station assembly during installation.
Available Modules
A Modicon M340 CPU can manage an entire rack. These three CPUs have Ethernet communication ports:
The BMX P34 20x0x CPUs can manage a station composed of:
NOTE: Refer to the Modicon X80 Racks and Power Supplies, Hardware, Reference Manual for specific part numbers.
Rack Position
The following rack assembly includes a Modicon M340 CPU (in this case a BMX P34 2030) and a BMX NOE 01•0 module (in this case a BMX NOE 0100). Rack positions 0 to 8 are indicated. (The double-wide power supply is mounted at the beginning of the rack.)
0 
BMX P34 2030 CPU at rack position 0
1 
discrete I/O module at rack position 1
2 
counter module at rack position 2
3 
BMX NOE 0100 Ethernet communications module at rack position 3
4-7 
available rack positions
8 
Modicon M340 extension module at rack position 8
Module Positioning
Mechanically, it is possible to position the BMX P34 CPU or the I/O modules in any slot. However, we recommend placing the modules in these positions:
BMX P34 20•0• Processors
The following table shows the rack operations and communications details for the BMX P34 20x0x CPUs:
CPU
Physical Format
Maximum Number of I/O*
Maximum Memory Size
Integrated Port
Discrete
Analog
CANopen
Ethernet
Modbus Serial
BMX P34 2020
simple
1024
256
4096 Kb
X
X
BMX P34 2030/20302
simple
1024
256
4096 Kb
X
X
*: per rack
X: available
—: not available