Communication type
|
Feature
|
Capacity
|
---|---|---|
EtherNet/IP (CIP Implicit Messaging)
|
Scanner
|
|
Maximum number of devices
|
128 devices (125 devices as scanner + 3 devices as adapter) shared with Modbus TCP
|
|
Maximum message size
|
512 bytes
|
|
Adapter
|
||
Maximum number of instances
|
3 adapter instances
|
|
Maximum number of connections
|
2 connections per instance
|
|
Maximum message size
|
511 bytes including header
|
|
Inputs
|
505 bytes excluding header
|
|
Outputs
|
509 bytes excluding header
|
|
Modbus TCP (Modbus Scanner)
|
Maximum number of registers
|
|
Read
|
125 registers
|
|
Write
|
120 registers
|
|
Maximum number of devices
|
128 devices shared with EtherNet/IP
|
|
Maximum message size
|
||
Read
|
250 bytes (125 words) excluding header
|
|
Write
|
240 bytes (120 words) excluding header
|
Communication type
|
Feature
|
Capacity
|
---|---|---|
EtherNet/IP (CIP Explicit Messaging)
|
Client
|
|
Maximum number of simultaneous connections
|
16 connections
|
|
Maximum number of concurrent requests
|
16 requests, shared with Modbus TCP
|
|
Server
|
||
Maximum number of simultaneous connections
|
32 connections
|
|
Maximum messaging size
|
1023 bytes
|
|
Modbus TCP (Modbus Scanner)
|
Client
|
|
Maximum number of simultaneous connections
|
16 connections
|
|
Maximum number of concurrent requests
|
16 requests, shared with EtherNet/IP
|
|
Server
|
||
Maximum number of simultaneous requests
|
128 requests
|
|
Maximum number of simultaneous connections
|
32 connections
|
|
Maximum message size
|
||
Read
|
250 bytes (125 words) excluding header
|
|
Write
|
240 bytes (120 words) excluding header
|