Introduction

To facilitate communications with the BMENOR2200H module, create data points for the IEC60870-5-101/104 communication protocols in the DATA MAPPINGS tab in the DTM.

Access the Configuration Tab

Access the configuration parameters on the DATA MAPPINGS tab in Control Expert:

Step

Action

1

Access the DTM configuration for your module.

2

Confirm that you already created client and/or server channels.

3

In the CONFIGURATION menu, expand (+) the Channels sub-menu.

4

Make one of the following selections in the Channels/Devices sub-menu:

  • IEC104 Client

  • IEC104 Server

  • IEC101 Client

  • IEC101 Server

5

Select the desired device in the sub-menu.

6

Select the DATA MAPPINGS tab for the channel.

7

Configure the data mapping parameters.

8

  • Select Apply to implement your configuration changes.

  • Select OK to implement your changes and close the dialog box.

IEC60870-5-101/104 Data Mappings

Edit the data point configuration on the DATA MAPPINGS tab:

Step

Action

1

Select a type ID in the Select Type Id drop-down list.

2

Select the Add button to configure the data object type.

3

Configure the data object type.

Depending on the data object type and the selected protocol profile, different configuration fields are required to define a data object mapping item.

4

  • Select Apply to implement your configuration changes.

  • Select OK to implement your changes and close the dialog box.

IEC60870-5-101/104 Data Mapping Parameters

NOTE: When the Control Expert window is active, you can hover the cursor over any field to see a description of the functionality and the available range of values.

This table describes the parameters:

Field

Client

Server

Value Scope

Default Value

Description

IOA

1~16777215

1

Indicates the information object address of the object.

Point Count

1...7000

1

Indicates the number of objects defined. The IOA of each object defined. The IOA of each object is in sequence from the first object address.

Variable Name

Max length: 32

M_SP_P1/...

Indicates the variable name.

CPU Reg Mapping

  • Value only

  • Value with time

  • Value with flag

  • Value with flag and time

Value only

Indicates the choice of the stored time or flag; follows the value in the CPU Device DDT variable.

Operation Mode

  • Auto

  • Select

  • Execute

  • Deselect

Auto

Indicates the operation mode for C_SC/C_DC/C_RC/C_SE_A/C_SE_B/C_SE_C control command.

  • Activation

  • Deactivation

Activation

Indicates the active/deactive operation for the C_IC/P_AC point.

  • Read

  • Freeze

  • Freeze with reset

  • Reset

Read

Indicates the operation mode for C_CI control command.

Qualifier

  • Default

  • Short Pulse

  • Long Pulse

  • Persistent Output

Persistent output

Indicates the qualifier for C_SC/C_DC/C_RC control command.

When it is received, a C_SC/C_DC/C_RC command with ‘default qualifier,’ the server operates the command with this configured qualifier.

G/1/2/3/4/5/6/7/8/9/10/11/12/13/14/15/16

G

Indicates the interrogation group for C_IC control command.

1/2/3/4/G

1

Indicates the counter interrogation group for C_CI control command.

  • General

  • Event

General

Indicates general reset or event clear for C_RP control command.

  • Threshold

  • Low limits

  • High limits

Threshold

Indicates the parameter type to set for P_ME_A/P_ME_B/P_ME_C point.

Threshold

0...32767

0

Indicates the default threshold value for M_ME_A/M_ME_B point to trigger event.

0~3.402823466385288E+38

0

Indicates the default threshold value for M_ME_C point to trigger event.

Low Limit

-32768...32767

—32768

Indicates the low limit value for M_ME_A/M_ME_B point to trigger event.

-3.402823466385288E+38~3.402823466385288E+38

—3.402823466385288E+38

Indicates the low limit value for M_ME_C point to trigger event.

High Limit

—3.4028823466385288E+38~3.402823466385288E+38

3.402823466385288E+38

Indicates the high limit value for M_ME_C point to trigger event.

-32768...32767

32767

Indicates the high limit value for M_ME_A/M_ME_B point to trigger event.

Read Number

1...16777215

1

Indicates the information object address of the point to be read.

Add CMD_STATUS

Check box

Selected

Specify the CMD_STATUS variable name.

Associate Point Number

104 max.: 16777215

101 max.: based on IOA size

1

Starting point number of the point.

Channel Mask

Check boxes

Selected

For each check box, specify the channel number to clear object group (dependent on the channel configuration).

Default Qualifier

  • Short Pulse

  • Long Pulse

  • Persistent Output

Persistent Output

Default qualifier of the command if the controlling station does not specify a qualifier.

Freeze Period

0...4294967295

2000

Specify the width of the pulse (ms).

M_ME_X Point Number

1...16777215

1

Specify the associated M_ME_X point parameter.

PLC State

No Impact Quality

Impact Quality

Specify whether the quality of monitoring points are impacted by the PLC state.

Type

(command types)

Select a command type.

Short Pulse Duration

0~4294967295 ms

100 ms

Indicates the short pulse duration for C_SC/C_DC/C_RC control point.

Long Pulse Duration

0~4294967295 ms

1000 ms

Indicates the long pulse duration for C_SC/C_DC/C_RC control point.

Need Select

Check box

Selected

Indicates the need to select before operation for C_SC/C_DC/C_RC/C_SE_A/C_SE_B/C_SE_C control command.

Cdc Mode

  • Determinate state

  • Indeterminate state

Determinate state

Indicates the pulse recovery state for C_DC command. In determinate state mode, it recovers to the previous on (2)/off (1) state. In indeterminate state mode, it recovers to the fixed intermediate (0) state.

Qualifier

  • Threshold

  • Low limits

  • High limits

Threshold

Indicates the parameter type to set for P_ME_A/P_ME_B/P_ME_C point.

Global 1/2/3/4/5/6/7/8/910/11/12/13/14/15/16

Check box

Global

Defines the data object group responding to the interrogation command from the client. It can be a combination of options.

Event Routing

Route Channel

Disable/Enable

Disable

Indicates whether the event routing function is disabled or enabled.

Route Session

0

0

Indicates the session number to route.

Route Sector

Server device list

First device

Indicates the device to route.

Route Point

1...16777215

1

Indicates the information object address to route.

Routing Offline

  • Valid Quality

  • Invalid Quality

Valid quality

Specifies the flag when routing channel is offline.

Background Scan

Check box

Deselected (disabled)

Indicates the background scan is enabled. (The check box is selected.)

Cyclic Data Transmission

Check box

Deselected (disabled)

Indicates the cyclic data transmission is enabled. (The check box is selected.)

Event Generation

Check box

Selected (fixed)

Indicates that events for points can be configured.