Add the Module to the PLC Bus
Add a BMENOR2200H advanced RTU module to a Control Expert project and assign a name to it:
Step |
Action |
|---|---|
1 |
Open a project in Control Expert. |
2 |
Expand (+) the to see the (). |
3 |
Double-click to view the assembled rack(s). |
4 |
Right-click an empty rack slot and scroll to select a . NOTE: Select a rack position that conforms
to the module’s slot restrictions.
|
5 |
In the column in the dialog box, expand to see the available modules. |
6 |
Double-click the BMENOR2200H module to open the dialog box. NOTE: There are several BMENOR2200H modules under the Device List. The later
versions correspond to the newer features from the software version.
We recommend that you select the latest version in the list and upgrade
the firmware in the BMENOR2200H module to the latest version that is appropriate for your hardware.
|
7 |
In the field, assign a name to the module (or accept the default name). |
8 |
Confirm that the DTM for the module was automatically added to the project (). NOTE: When you add a module to the local rack configuration, the corresponding
communication DTM is automatically added to the list ().
|
9 |
Repeat these steps to add more BMENOR2200H modules to the . NOTE: The local rack in an M580 system can hold a maximum of four communication
modules, including RTU modules.
|