Enable service port configuration:
Step
|
Action
|
1
|
|
2
|
Select Service Port in the navigation tree.
|
3
|
In the Service Port Mode list, select:
-
Access Port (default)
-
Port Mirroring
-
Extended Network
|
4
|
Press a button to finish:
|
In Access Port mode, the service port is Enabled and cannot be changed. Connect these types of devices to the service port in this mode:
You can communicate with the CPU/ or the BMENOC0321 module itself. You can also access other devices that are connected to the network.
Select Port Mirroring mode to configure the port to monitor and capture traffic to support a network analyzer (like Wireshark). In this mode, the service port is a read-only port. That is, you cannot communicate with Ethernet devices through the service port.
In the Port Mirroring area, use the Source Port property to enable specific ports:
The service port monitors traffic to the enabled ports:
Source Port
|
Description
|
Internal Port
|
Monitor Ethernet traffic to and from the module via the service port.
|
ETH 2
|
Ethernet traffic to and from port ETH 2 is sent to the service port.
|
ETH 3
|
Ethernet traffic to and from port ETH 3 is sent to the service port.
|
Backplane Port
|
Ethernet traffic to and from the backplane port is sent to the service port.
|
NOTE: If a device that is connected to the service port, ETH 2 port, or ETH 3 port is configured for a speed that exceeds 100 Mbps, the Ethernet link may not be established between the device and the module through the service port.
Select this mode to extend the device network.
Add an extended DIO network to an M580 system by following the directions in the
Modicon M580 Standalone System Planning Guide for Frequently Used Architectures.
Configure the service port online with Control Expert using
CIP explicit messaging, but this configuration may be lost when the BMENOC0321 Ethernet communications module is reset.
Configure the service port online with Control Expert using CIP explicit messaging. Refer to the description of the
service port control object The CIP object configuration is stored in volatile memory. When the BMENOC0321 Ethernet communications module is reset it reverts to the service port configuration in the DTM (above)