Prerequisites
 
Update Operation and Associated Connections
Main operations performed to update a CPU with an Ethernet coprocessor:
Operation
Communication protocol
Connect the PC to the Ethernet port or the CPU.
FTP (Ethernet)
Update the Ethernet port coprocessor firmware.
Connect the PC to the Modbus or Modbus Plus port of the CPU.
Modbus
Modbus Plus
Update the CPU OS.
Coprocessor Update Presentation
To update the coprocessor, you have to use OS Loader.
The CPU OS version needs to be at V 2.31 or later before the Ethernet port update.
Coprocessor Default IP Address
If the Ethernet port of the coprocessor is not configured in the Unity Pro application, it takes the IP address built from its MAC address:085.016.xxx.yyy where xxx and yyy are the last two values of the Ethernet port MAC address.
For example, if the MAC address is: 00.80.F4.01.12.20 in hexadecimal, the corresponding default IP address is: 085.016.018.032 in decimal.
IP Address of the PC
Change the IP address of your PC to get it into the same subnetwork as the CPU.
The first three groups of digits have to be the same. For example, the CPU address is 85.16.133.13 and the PC address needs to be 85.16.133.xx.
Physical Connection
Connect your PC to the CPU Ethernet coprocessor for the update.
Make a minimal configuration with no TCP traffic as indicated in the section Connecting the PC to an Ethernet Module or Coprocessor.