Step
|
Action
|
---|---|
1
|
Click Start → Program → Schneider Electric → Unity Loader to launch Unity Loader.
|
2
|
Select the Firmware tab:
![]() |
3
|
In the Connection dialog box, select the media in accordance with the chosen physical connection:
|
4
|
Click Connect.
NOTE: The connection is confirmed when the Connect button changes to Disconnect button. If the button does not change, verify that the CPU, BMX NOE 01•0, or module is turned on and the physical connection is correctly set. |
5
|
Stop the CPU.
|
6
|
Depending on the device to update, proceed as follows:
CPU:
In the PLC dialog box, select the CPU to be updated in the window list.
BMX NOE 01•0:
In the PLC dialog box, select the BMX NOE 01•0 module to be updated in the window list.
Module that can be updated:
In the PLC dialog box:
|
7
|
In the PC dialog box, click
![]() |
8
|
Select the appropriate *.ldx firmware file and click Open.
|
NOTICE
|
EQUIPMENT DAMAGE
During the download:
Failure to follow these instructions can result in equipment damage.
|
Step
|
Action
|
---|---|
1
|
After selecting the appropriate *.ldx firmware file in the Firmware tab of Unity Loader, check if the firmware of the PC is:
|
2
|
Check that the SD card is plugged in if one of the following devices is updated:
|
3
|
Click Transfer.
Result: A Security Advice popup window is displayed.
|
4
|
Check that:
|
5
|
Click Yes to start downloading the firmware file.
Result: The Transferring data to PLC window is displayed with the remaining time. The duration depends on the protocol used and the PC configuration.
|
6
|
In the Transferring data to PLC window, check if the download is completed.
Result: The Firmware upgraded successfully message is displayed when the download is completed.
NOTE: If this message is not displayed, check each step and contact your local Schneider Electric office for assistance. |
7
|
Click Close.
Result: The device is automatically reset once the download of the firmware file is completed.
|
Step
|
Action
|
---|---|
1
|
Connect the PC to the device.
|
2
|
Launch Unity Loader software.
|
3
|
Select the Firmware tab.
|
4
|
Establish a connection with the device.
|
5
|
In the PLC dialog box, check the version displayed.
|