Check whether the following conditions have been adhered to before starting the configuration:
-
Can be used in local or remote racks (RIO) with RIO Drop Firmware higher than V1
-
Cannot be used in DIO Drops
-
Up to 9 ERTs can be mounted on each remote (RIO) drop
-
Processing signal status > 1 millisecond + filter time possible
-
Counter inputs up to 500Hz with 32 bit
-
Each ERT requires an "ERT_854_10" transfer EFB
-
7 INPUT words, 5 OUTPUT words per ERT
-
Several ERT modules can be connected to one standard time receiver. The 140 ERT 854 10 requires 5 mA from the receiver
-
Maximum power consumption of 0.07mA from the battery module XCP 900 00 required for receiving counter, event FIFO buffer and parameter data.
The standard time receiver must provide an output signal in DCF77 format for 24 VDC.
The following standard time receivers are provided: