Reference voltage for each process input group
|
24 ... 125 VDC, (max. 18 ... 156 VDC) Current consumption per group: max. 20 mA
|
internal via the rack
|
5 VDC, max. 300 mA
|
Current requirements for buffer operation
|
maximum 0.07 mA from XCP 900 00
|
Number
|
32 in 2 Groups
|
|||
Input Voltage
|
24 ... 125 VDC
|
|||
Potential isolation
|
Inputs to the Quantum Bus, Group 1 to Group 2 (Opto-coupler)
1780 VAC for 1 minute
|
|||
Debounce time
|
0 ... 255 milliseconds (configurable)
|
|||
Inversion
|
Set with parameters
|
|||
Max. Cable length
|
400 m unshielded, 600m shielded
|
|||
Switching Level:
Nominal voltage for the input signals
Min current for a 1 signal
|
24V
6mA
|
48V
2.5mA
|
60V
2.5mA
|
125V
1mA
|
Signal level 0 signal
Signal level 1 signal
|
nominal 0% of the group reference voltage,
max. +15 %, min. -5 %
nominal 100% of the group reference voltage,
max. 125 %, min. 75 %
|
|||
Internal power loss from all process inputs
|
max 7.5 W
|
Number
|
1, DCF77 Data format from DCF- 077E
|
Input Voltage
|
24 VDC
|
Potential isolation
|
Optocoupler
|
Time Stamp resolution
|
1 ms
|
Current consumption
|
5 mA
|
Format
|
Width = 40.34 mm (Standard Housing)
|
Mass (weight)
|
0.45 kg
|
Process Inputs, DCF receiver
|
40 pins Terminal Block
|
System Data
|
See Quantum User Manual
|
Power loss
|
Max. 9W, typical 5W
|