Communication Protocols
Original instructions
Introduction
This topic describes the characteristics of the supported RTU protocols.
Functions and Protocols
The BMXNOR0200H module supports these functions and protocols:
RTU protocols
IEC 60870-5-101 (master or slave)
IEC 60870-5-104 (client or server)
DNP3 serial (master or slave)
DNP3 NET (client or server)
Main RTU protocol features
time synchronization through a protocol facility or NTP
balanced and unbalanced transmission mode
events management with time stamping
events queue stored in RAM memory (up to 100,000 events for all clients)
events data backfill to SCADA application via protocol facility
report by exception data exchanges
unsolicited messaging data exchanges
protocol setup via webpage
NOTE: The RTU protocol parameters are configured using the embedded webpages.
Limitations
The BMXNOR0200H module does not support multiple RTU protocols instances. Only one instance at a time of an RTU protocol (IEC, DNP3) can be launched to work with Modbus TCP.
NOTICE
UNINTENDED EQUIPMENT OPERATION
  • Use different address values for each session in a channel or for each section in a session.
  • Channel parameters must meet IEC60870-5-104 protocol requirements with these limitations: T2 S Frame Period < T1 Ack Period and W Value < 2/3 K Value.
  • If you are using the DNP3 protocol, use successive DB mapping starting at 0.
Failure to follow these instructions can result in equipment damage.