Configuring with Control Expert
Original instructions
Module Reference
Find the module reference in Control Expert:
Step
Action
1
Open the PLC Bus view.
2
Right-click on an empty slot and select New Device.
3
In the Part Number column, expand Communication to see the available modules, including the BMXNOR0200H.
NOTE: In a Modicon M340 system the total number of communication modules, such as BMX NOE 01•0 or BMXNOR0200H modules, cannot exceed two. The maximum Ethernet port for M340 system is 3 including the port on PLC. Therefore, a maximum of two BMXNOR0200H modules can be inserted in a M340 system.
NOTE: For Modicon M580 system module limitations, refer to topic System Throughput Considerations.
New Device
The module is referenced as a BMX NOR 0200 in Control Expert. It is available under Communication in the New Device menu:
Only Ethernet port (channel 0) is configurable in Control Expert. Serial port is configured through the Web.
The Control Expert description for this module is “Ethernet TCP/IP, RTU module”: